Description
Dilock is a safety device that quickly interrupts the gas flow should the controlled pressure reach the intervention set valve due to any malfunction.
Special suitable for natural gas, LPG and non-corrosive gas.
Features- Intervention for over/under pressure or for overpressure only
- Intervention for temperature increase within 170°/190° C - 338°/374° F
- Manual reset
- Compact
- Reduced size
- Can be maintained regularly without removing body from pipelines
- Integrated by-pass
- Installed with pressure switch on bottom
Specifications
Specifications
Hydrogen Compatibility %
Hydrogen Compatible up to 100% Hydrogen Compatible up to 30% Hydrogen Compatible up to 20%
Accuracy Class
- AG 5/10/20 %
- AG 10/20/30 %
Maximum Inlet Pressure
- 18.9 bar
Operating Temperature
- -10° to +60° C
Ambient Temperature
- -20° to +60° C
Range of Outlet Pressure Wh
- 30 to 5,500 mbar
Threaded Connections
- UNI-150 7 Rp
Flanging Connections
- Class 150RF Acoording to ANSI B 16.5 and PN 16 According to ISO 7005