Images are representations only.

Aperval Pressure Regulator

Brand: Pietro Fiorentini S.p.A.
When requesting information, please download the Fillable PDF to provide details about your regulator use case. Instructions for completing the form are found in the footer of the document. Once completed, please upload the document with the Request for Information.
Aperval is a pilot-controlled pressure regulator for medium and low pressure applications.

Aperval is normally a fail open regulator and will open specifically under the following conditions:
  • If the main diaphragm fails
  • If there is no sensor line input
This regulator is suitable for use with previously-filtered, non-corrosive gases.
Features
  • Design pressure: up to 362 PSIG (25 bar) 
  • Temperature: Pietro Fiorentini regulators are suitable for a minimum operating ambient temperature: 
    • -40° to 140° F with a Carbon Steel Body
    • -4° to 140° F with a Cast Iron Body
  • If the following conditions are met: 
    • Inlet flowing gas temperature shall be always higher than -4° F
    • Inlet flowing gas shall be filter, clean and without any liquid impurities
  • Range of inlet pressure bpe: 7.25 to 362 PSIG (0.5 to 25 bar) 
  • Range of outlet pressure Wh: 2” w.c. to 137.5 PSIG (5 mbar to 9,500 mbar) depending on installed pilot 
  • Minimum working differential pressure: 6.52 PSIG (450 mbar) 
  • Maximum working differential pressure: 275.5 PSIG (19 bar) 
  • Accuracy class AC: up to 2.5 > Closing pressure class SG: up to 5 
  • Available size DN: 1”, 2”, 2-1/2", 3”, 4” 
  • Flanging: class 150 RF or RTJ according to ANSI B16.5 and PN25/40 according to ISO 7005
show more
Aperval is a pilot-controlled pressure regulator for medium and low pressure applications.

Aperval is normally a fail open regulator and will open specifically under the following conditions:
  • If the main diaphragm fails
  • If there is no sensor line input
This regulator is suitable for use with previously-filtered, non-corrosive gases.
Features
  • Design pressure: up to 362 PSIG (25 bar) 
  • Temperature: Pietro Fiorentini regulators are suitable for a minimum operating ambient temperature: 
    • -40° to 140° F with a Carbon Steel Body
    • -4° to 140° F with a Cast Iron Body
  • If the following conditions are met: 
    • Inlet flowing gas temperature shall be always higher than -4° F
    • Inlet flowing gas shall be filter, clean and without any liquid impurities
  • Range of inlet pressure bpe: 7.25 to 362 PSIG (0.5 to 25 bar) 
  • Range of outlet pressure Wh: 2” w.c. to 137.5 PSIG (5 mbar to 9,500 mbar) depending on installed pilot 
  • Minimum working differential pressure: 6.52 PSIG (450 mbar) 
  • Maximum working differential pressure: 275.5 PSIG (19 bar) 
  • Accuracy class AC: up to 2.5 > Closing pressure class SG: up to 5 
  • Available size DN: 1”, 2”, 2-1/2", 3”, 4” 
  • Flanging: class 150 RF or RTJ according to ANSI B16.5 and PN25/40 according to ISO 7005

Specifications

Accuracy Class

  • Up to 2.5

Available Size DN

  • 1”
  • 2”
  • 2-1/2”
  • 3”
  • 4”

Closing Pressure Class SG

  • Up to 5

Design Pressure

  • Up to 25 bar (362 psig)

Design Temperature

  • -10° to 60° C (14° to 140° F)

Flanging

  • 150 RF or RTJ According to ANSI B16.5 and PN 25/40 According to ISO 7005

Maximum Working Differential Pressure

  • 19 bar (275.5 psig)

Minimum Working Differential Pressure

  • 450 mbar (7.25 psig)

Outlet Pressure Range of Wd

  • 5 mbar to 9,500 mbar (2” w.c. to 137.5 psig)

Range of Inlet Pressure Bpu

  • 0.5 to 2.5 bar